Jola Spezialschalter K. Mattil
& Co. KG
Klostergartenstraße 11-20 D-67466 Lambrecht Phone: +49 63 25 / 188-01 |
Plate electrode
PEK-Z10
|
|
|
|
|
|
![]() |
|
For signalling the presence of an electrically conductive liquid caused, for example by burst pipes. Plate electrodes can, for example, be used on normally dry floors or false ceilings or in normally dry pipeline and cable ducts. If the two electrode plates of a plate electrode come into contact with an electrically conductive liquid (e.g. water, acid etc.), an electrical contact is made and an alarm signal given. Electrode plates, material: stainless steel 316 Ti |
|
| Brochure Conductive leakage detectors of the Leckstar range [PDF] | |
| |
|
| Control electrode | 1 |
| Earth electrode | 1 |
| Electrical connection / Connecting cable |
green halogen-free connecting cable, 2 x 0,75 |
| Cable length |
2 metres, longer cable on request |
| Housing |
PP and cast resin |
| Temperature resistance |
- 20° C to + 60° C |
| Documents | Installation, operating and maintenance instructions [PDF] |
| |
|
The plate electrode is fitted with two separate electrodes in the form of two electrode plates: 1 control electrode and 1 earth electrode. As soon as a trace of a conductive liquid creates a conductive path between the two electrode plates, a control current flows from the corresponding electrode relay. The latter is then energised and a contact made. The PE-Z10 or PEK-Z10 plate electrode or the plate electrodes combination PE + PE-Z10 or PE + PEK-Z10 may only be connected to the Leckstar 101 electrode relay. The connection must be made in line with the circuit diagrams. Max. length of connecting cable between plate electrode and electrode relay: 1,000 m. |
|
| Measure drawing |
| Application example |
| Basic circuit |
| Basic circuit 2 |