Level controllers Leakage detectors Other Jola products Search via product names Control of the chemical resistance
General information on Jola Quality management system Addresses: Jola and its agents Help on CD-ROM catalogue
Mercury-free immersion probe

TS/Ö/. x SSP 3/K/PVC

  • . = number of mounted floating switches 
    
    For automatic control of liquid levels
  • with screw-in nipple G2

 
For applications up to max. AC 250 V

Particularly suitable for fuel oil tanks, diesel-fired emergency power generators and
hydraulic oil tanks.

Application in liquids with a specific density >=0.82 g/cm³
Brochure Mercury-free floating switches and immersion probes [PDF]

Switching voltage AC min. 24 V
Switching voltage AC max. 250 V
Switching voltage DC min.  24 V
Switching voltage DC max.  250 V
Switching current AC min. 20 mA
Switching current AC max.  3,000 mA
Switching current AC max.
(inductive loads)
1,000 mA
Switching current DC min.  20 mA
Switching current DC max.  100 mA
Switching capacity AC max.  350 VA
Contact
ball-operated microswitch,
potential-free changeover contact
Probe tube material PP
Probe tube diameter min. 20 mm
(depending the number of mounted
floating switches)
to
Probe tube diameter 25 mm
Float material PP
Seal material FPM
Float protection class IP 68
Float form cylindrical float
Float diameter 29 mm
Float length 133 mm
Mounting orientation vertical
Mounting from the top
Type of mounted floating switches SSP 3/K/PVC

Number of mounted floating switches 5
Connecting cable
black PVC cable, 3 x 0,75
Application range of the
connecting cable
for water, used water, slightly aggressive
liquids, oils without aromatic additives, 
fuel oil and diesel fuel
Screw-in nipple material PP
Screw-in nipple dimension G2
Housing
A 307 made of PP, 120 x 80 x 55 mm, 
protection class IP 65

for more than 12 terminals:
terminal box made of polyester, A 113, 
160 x 160 x 90 mm, protection class IP 65
Temperature
application range
8° C to + 60° C
Pressure resistance
for pressureless applications

Probe tube length: according to customer's specifications

On request: 
- with more than 5 mounted float switches
- with screw-in nipple G1½, G2 or G2 adjustable
Functional description based on a switching example:

Automatic filling of a tank
The bottom floating switch falls together with the liquid to a minimum level and acts on the 
contactor coil winding when it falls below the horizontal. Liquid is then pumped into the tank. 
When the maximum level is reached, the top floating switch rises above the horizontal, the 
contactor holding circuit is interrupted, and the filling process is stopped.

The above equipment will be manufactured in accordance with customer's specifications.

Please always state desired floating switch type when ordering.

For technical data of mounted floating switches see corresponding pages.

This unit is not suitable for use in turbulent liquids (e.g. in stirrer tanks).

 

Top