Jola Spezialschalter K. Mattil
& Co. KG
Klostergartenstraße 11-20 D-67466 Lambrecht Phone: +49 63 25 / 188-01 |
Immersion probe with probe tube made of stainless steel and float
made of stainless steel
TSR/3/ED/E5
|
|
|
|
![]() |
|
For applications up to max. AC 250 V Float suitable for use in media with a specific density >=0.7 g/cm³ |
|
| Brochure Magnetically operated immersion probes TSR and TSM [PDF] | |
| |
|
| Switching voltage AC min. | 24 V |
| Switching voltage AC max. | 250 V |
| Switching voltage DC min. | 24 V |
| Switching voltage DC max. | 250 V |
| Switching current AC min. | 100 mA |
| Switching current AC max. | 2,000 mA |
| Switching current AC max. (inductive loads) | 400 mA |
| Switching capacity AC max. | 100 VA |
| Probe tube material | stainless steel 316 Ti |
| Probe tube diameter max. | 12 mm |
| Probe tube length max. | 3,000 mm |
| Screw-in nippel material | stainless steel 316 Ti |
| Screw-in nippel dimension | G½ |
| Float material | stainless steel 316 Ti |
| Float form | ball float |
| Float diameter | 97 mm |
| Terminal box |
A 307 made of PP, 120 x 80 x 55 mm, protection class IP 65, for max. 12 terminals |
| Mounting orientation | vertical |
| Mounting | from the top |
| Temperature resistance |
- 20° C to + 100° C |
| Pressure resistance |
Pressure resistance at + 20° C: max. 12 bar, higher pressure resistance on request |
| Contact |
reed contacts: make (NO), break (NC) or changeover (OC) contact |
| Max. number of contacts | 3 |
|
Min. distances to be observed |
90 mm |
| between contacts | 80 mm |
| from the lower contact to
the end of the probe tube (when float is falling) |
60 mm |
| Questionnaire | Questionnaire for inquiries or orders [PDF] |
| |
|
Probe tube length: according to customer's specifications, however max. 3,000 mm Screw-in nipple: on request G1, G1½ or G2; on request with reducing nipple made of malleable cast iron R1½ or R2 conical or made of cast steel G2 Other terminal boxes and with free connecting cable in place of terminal box on request Also available with angled probe tube for mounting from the side |
|
The above equipment will be manufactured in accordance with customer's specifications
|
|
| Measure drawing |
| Top |