Immersion probes TSR EEx

Magnetically operated automatic liquid level controls

Tauchsonden TSR, RN und TSM



Magnetically operated automatic liquid level controls

Construction and operating principle of TSR immersion probes

The TSR immersion probes have a probe tube with built-in reed contacts. The float is fitted with a permanent ring magnet and moves freely up and down the probe tube, activating the reed contacts as it rises and falls. It should be noted that reed contacts do not lock but that they switch only for as long as they are influenced by the magnetic field. Once the float passes beyond a contact upwards or downwards, the latter returns to its original position. However, the contacts can be made to hold by using collars to limit the motion of the float.


Typemap:

Probe tube
made of
stainless steel
316 Ti

Float made of
stainless steel 316 Ti
Types
Connection
Ø
Outer dimension
TSR/ED/E./Variante 0/Ex-0
II 2/1 GD EEx ia IIC T6


TSR/EW/E5/Variante 0/Ex-0
II 2/1 GD EEx ia IIC T6
Terminal box
12 mm



20 mm

E1 : Ø 73 mm (ball)
E2 : Ø 44.5 mm x 52 mm
E3 : Ø 52 mm x 85 mm
E5 : Ø 97 mm (ball)


Ø 97 mm (ball)

TSR/FED/E./Variante 0/Ex-0G
II 1 G EEx ia IIC T6


TSR/FEW/E5/Variante 0/Ex-0G
II 1 G
EEx ia IIC T6
Terminal box
12 mm


20 mm
E1 : Ø 73 mm (ball)
E2 : Ø 44.5 mm x 52 mm
E3 : Ø 52 mm x 85 mm
E5 : Ø 97 mm (ball)


Ø 97 mm (ball)

TSR/FHED/E4/Variante 0/Ex-0G
II 1 G EEx ia IIC T4

TSR/FHEW/E4/Variante 0/Ex-0G
II 1 G EEx ia IIC T4
Connecting cable
14 mm


20 mm
97 mm Ø x 80 mm
TSR/FHED/E4/Variante 0/Ex-0G
II 1 G EEx ia IIC T3

TSR/FHEW/E4/Variante 0/Ex-0G
II 1 G EEx ia IIC T3
14 mm


20 mm
97 mm Ø x 80 mm
TSR/FED/E./EEx d/Ex-1
II 2 GD EEx d IIB T6


TSR/FEW/E5/EEx d/Ex-1
II 2 GD
EEx d IIB T6
12 mm


20 mm
E1 : Ø 73 mm (ball)
E2 : Ø 44.5 mm x 52 mm
E3 : Ø 52 mm x 85 mm
E5 : Ø 97 mm (ball)


Ø 97 mm (ball)

TSR/FHED/E4/EEx d/Ex-1
II 2 GD EEx d IIB T4

TSR/FHEW/E4/EEx d/Ex-1
II 2 GD EEx d IIB T4
14 mm


20 mm
97 mm Ø x 80 mm
TSR/FHED/E4/EEx d/Ex-1
II 2 GD EEx d IIB T3

TSR/FHEW/E4/EEx d/Ex-1
II 2 GD EEx d IIB T3
14 mm


20 mm
97 mm Ø x 80 mm



These units must only be mounted and connected by a qualified specialist personnel.
Manufacturer reserves the right to alter the design and the technical data at his own discretion.
The details in this brochure are product specification descriptions and do not constitute assured properties in the legal sense.